Spezifikationen
Nominal Voltage |
12 V |
||
Capacity (25℃) |
10HR(10.8V) |
250 Ah |
|
5HR(10.5V) |
219Ah |
||
1HR(9.60V) |
155Ah |
||
Dimension |
Length |
521±2mm (20.51inch) |
|
Width |
269±2mm (10.59inch) |
||
Height |
220±2mm (8.66inch) |
||
Total Height |
T5: 242±2mm (9.53inch) |
||
T11: 223±2mm (8.78inch) |
|||
Approx. Weight |
73kg (160.9lbs)±3% |
||
Terminal type |
T5/T11 |
||
Internal resistance (Fully charged, 25℃) |
Approx. 2.6mΩ |
||
Capacity affected by temperature (10HR) |
40℃ |
102% |
|
25℃ |
100% |
||
0℃ |
85% |
||
-15℃ |
65% |
||
Self-discharge (25℃) |
3 month |
Remaining Capacity: 91% |
|
6 month |
Remaining Capacity: 82% |
||
12 month |
Remaining Capacity: 65% |
||
Nominal operating temperature |
25℃±3℃(77℉±5℉) |
||
Operating temperature range |
Discharge |
-15℃~50℃(5℉~122℉) |
|
Charge |
-10℃~50℃(14℉~122℉) |
||
Storage |
-20℃~50℃(-4℉~122℉) |
||
Float charging voltage(25℃) |
13.50 to 13.80V Temperature compensation: -18mV/℃ |
||
Cyclic charging voltage(25℃) |
14.50 to 14.90V Temperature compensation: -30mV/℃ |
||
Maximum charging current |
75A |
||
Terminal material |
Copper |
||
Maximum discharge current |
1800A(5 sec.) |
||
Designed floating life(20℃) |
12 years |
||
◆ Absorbierende Glasmatte Technologie;
◆ Von UL & CE anerkannt;
◆ ABS-Behälter.
Konstante Stromentladungseigenschaften (A, 25 ℃ )
F.V/TIME |
15min |
30min |
60min |
2h |
3h |
4h |
5h |
6h |
8h |
10h |
20h |
9.60V |
413 |
250 |
155 |
91.4 |
63.8 |
52.3 |
44.6 |
39.0 |
30.6 |
25.5 |
13.4 |
9.90V |
403 |
245 |
153 |
90.8 |
63.4 |
52.0 |
44.4 |
38.8 |
30.4 |
25.4 |
13.3 |
10.2V |
388 |
238 |
149 |
90.0 |
62.9 |
51.6 |
44.1 |
38.5 |
30.2 |
25.3 |
13.3 |
10.5V |
375 |
232 |
146 |
88.7 |
62.5 |
51.3 |
43.8 |
38.3 |
30.0 |
25.2 |
13.2 |
10.8V |
355 |
223 |
141 |
86.4 |
60.6 |
49.7 |
42.4 |
37.1 |
29.1 |
25.0 |
13.1 |
Konstante Leistungsentladungseigenschaften (Watt, 25 ℃ )
F.V/TIME |
15min |
30min |
60min |
2h |
3h |
4h |
5h |
6h |
8h |
10h |
20h |
9.60V |
4529 |
2805 |
1767 |
1058 |
750 |
615 |
527 |
461 |
364 |
304 |
160 |
9.90V |
4421 |
2749 |
1740 |
1052 |
745 |
611 |
524 |
458 |
361 |
303 |
160 |
10.2V |
4257 |
2665 |
1696 |
1042 |
740 |
607 |
521 |
455 |
359 |
302 |
160 |
10.5V |
4113 |
2600 |
1663 |
1027 |
735 |
603 |
517 |
452 |
356 |
301 |
159 |
10.8V |
3895 |
2505 |
1612 |
1001 |
713 |
585 |
502 |
439 |
346 |
299 |
158 |
Hinweis: Die obigen Kenndaten können innerhalb von drei Lade- / Entladezyklen erhalten werden.